4.4 Internal Monitoring
Monitored values Criteria Function
Vi<: The device automatically switches off
with an adjustable delay time**. It switches on
if the input voltage is in the correct range. The
switch-on voltage is adjustable*.
DC input voltage
Input voltage out of the range of
adjustable thresholds Vi<* and Vi>*
Vi>: The device automatically switches off
without delay time (protection against
overvoltage). It switches on if the input
voltage is lower than the adjusted switch off
threshold*.
AC output voltage
Output voltage higher than adjusted
operating threshold*
Output voltage lower than adjusted
operating threshold*
The device automatically switches off; manual
restart is necessary.
LED “Vo” = OFF; LED “collective failure”= ON
AC output current
>130% Inom
>100% Inom
LED “Io>” = ON; After 3 seconds the device
automatically switches off; automatic restart
after 15 seconds (for 3 times).
After 30 seconds follows an automatic
shutoff; manual restart is necessary.
Overheating;
Cooling fan
function
Internal temperature higher than
adjusted threshold (factory setting)
The device automatically switches off with
delay time. It automatically switches on if the
temperature is lower than adjusted switch on
threshold. LED T> is on.
Additionally the fan voltage and current
characteristic is monitored to detect a
defective fan. This is indicated by a blinking
LED T>.
* Adjustment of the threshold values please see section 4.5 //**Only with the service menu PM2.