DC/AC Inverter
UNV-F
User Manual
Page 21 (28)
©2009. ELTEK VALERE DEUTSCHLAND GmbH. UM_UNVF_ E_R2.0
4.5.3 Table “Adjustable Parameters”
Following table shows the standard values (factory set), adjustment ranges and steps:
Display1 Designation Factory setting Range Step

nominal value of output
voltage Uo
230 [VAC] 200...255
0,25 [V] *

monitoring threshold of
output voltage low Uo<
207 [VAC] 180...230 1,0 [V]

Monitoring threshold of
output voltage high
Uo>
253 [VAC] 230...270 1,0 [V]

switch off threshold
input voltage high Ui>
48/60V: 75 [VDC]
108V: 130
0...80
0...135
0,1 [V]
0,25 [V]*

switch off threshold
input voltage low Ui<
48V: 41 [VDC]
60V: 51 [V
DC]
108V: 92 [V
DC]
41...80
41...80
90...110
0,1 [V]
0,1 [V]
0,25 [V]*

switch on again
threshold input voltage
low Ui<
48V: 45 [VDC]
60V: 56 [V
DC]
108V: 96 [V
DC]
41...80
41...80
90...110
0,1 [V]
0,1 [V]
0,25 [V]*

CAN Address 001 1
*When adjusting the threshold values with up/down keys, the moving dot shows the actual value according to
the example (this applies only to the 0.25 steps):
Example:

corresponds to 230.0

corresponds to 230.25

corresponds to 230.5

corresponds to 230.75
With each click at the UP/Down keys the dot moves. After four times clicking (4/4), the voltage value is
increased (or decreased) for 1V.