28 User Manual THEIA HE-t String Inverters 357115.013, Issue 1.0, 2011 March
2. Stringbox with DC Fuse Holders and no DC Switch
The Stringbox can be equipped with DC fuse holders and plug-in connectors or cable glands,
but no DC switch. A DC switch must be installed separately by qualified persons in
compliance with the relevant local and national electrical regulations.
Figure 4.3.8: Optional DC connectors and no DC
switch
P1, P2, P3:
Positive connectors
N1, N2, N3:
Negative connectors
BP: Blanking Plug
Figure 4.3.9: Stringbox with DC fuse holders and
blanking plug
*N4:
Grounding terminal and terminal for the
grounding strap
*P4:
Ungrounded terminal
Positive grounded PV String
• Connect the positive connectors from the positive connectors to the terminal block labeled
Grounded, and the negative conductors to the terminal block labeled Ungrounded.
• Switch the conductors connected to *N4 and *P4.
• Connect the grounding strap between *N4 and the DC ground terminal in the customer
connection area (See 4.3.3. Grounding).
Negative grounded PV String
• Connect the grounding strap between *N4 and the DC ground terminal in the customer
connection area (See 4.3.3. Grounding).