User Manual THEIA HE-t String Inverters 357115.013
,
Issue 1.0, 2011 April
35
Connection Procedures
Figure 4.3.15: Customer connection area with AC terminals
1. AC terminal block:
GND: Ground terminal
N: Neutral terminal (TN/TT)
or Phase terminal (IT)
L: Phase terminal
2. Cable gland
The current carrying conductors on the AC side must be rated for the current and have a
cross section area of maximum 16 mm
2
/ 6 AWG. Ensure compliance with the relevant local
and national electrical regulations!
The AC conductor resistance should be minimized by selecting as large a size of cable
cross-section area as possible, up to 16 mm
2
/ 6 AWG.
Unscrew the cable gland locknut.
Guide the AC cable through the opening, and connect the conductors to the corresponding
terminals in the connection area:
Phase conductor (L1 or L2 or L3) to L
Neutral conductor (TN/TT) or Phase conductor (IT) to N
Grounded conductor to GND
Tightening torque of the terminals is 1.5 Nm / 1.11 ft-lbf.
Double check if the connection is correctly carried out.
Hand-tighten the gland locknuts to seal the cable gland.
4.3.6. Network Connections
The inverter is equipped with two network interfaces; Ethernet and CAN. Ethernet provides
communication between the integrated web server and a computer, either directly connected
or via a router/switch. CAN allows communication between several inverters.
Figure 4.3.16: Network connections
1. Slave inverter
2. Master inverter
3. CAN
4. Ethernet
5. Computer