Installation Guide THEIA HE-t String Inverters 357115.033, Issue 2.0, 2011 March 11
Ensure that the inverter is correctly mounted, and tighten the lock clip with one screw into
the inverter and one into the string box (if present).
Recommended torque is 1.0 Nm / 0.74 ft-lbf.
2.3. Electrical Installation
Correct electrical connection is critical for achieving a safe, long-term and reliable operation
of the entire PV system.
DANGER: Never work with live wires!
All work on the inverter must be performed with disconnected terminals, as contact
with live wires may cause serious injury or death!
DANGER: Ensure correct electrical connections!
Connection of the AC and DC side must be performed by qualified persons and
comply with local and national electrical regulations and the instructions detailed in
this Installation Guide.
Ensure that the conductors and circuit breakers are properly sized to comply with the ratings
of the circuits and the national electrical regulations to avoid possible damage.
The conductors must be listed for PV applications and the site environment and have the
correct color coding to avoid material damage and bodily harm.
2.3.1. Connection Area
The DC connection can be configured in three different ways; either by using a stringbox
with fuse holders, a stringbox with no fuse holders or no string box.. The configuration of the
AC connections and the network connections are the same regardless of the different DC
connection options.
Prior to the electrical connection the lower inverter cover must be removed (See 1.3.3.
Inverter Structure).