Installation Guide THEIA HE-t String Inverters 357115.033, Issue 2.0, 2011 March 21
2.3.4.1. Connection Procedures
Figure 2.3.14: Customer connection area with AC terminals
1. AC terminal block:
GND: Ground terminal
N: Neutral terminal (TN/TT)
or Phase terminal (IT)
L: Phase terminal
2. Cable gland
The AC conductors must be sized for the correct temperature and sunlight resistance. Use
copper wire with a maximum cross-section area of 16 mm
2
/ 6 AWG. Ensure compliance
with the relevant national electrical regulations!
The AC conductor resistance should be minimized.
Unscrew the cable gland locknut.
Guide the AC cable through the opening, and connect the conductors to the corresponding
terminals in the connection area:
Phase conductor (L1 or L2 or L3) to L
Neutral conductor (TN/TT) or Phase conductor (IT) to N
Grounded conductor to GND
Tightening torque of the terminal screws is between 1.2-1.5 Nm / 0.89-1.11 lbft.
Double check if the connection is correctly carried out.
Hand-tighten the gland locknuts to seal the cable gland.
2.3.5. Network Connections
The inverter is equipped with two communication interfaces; Ethernet and CAN. Ethernet
provides communication between the integrated web server and a computer, either directly or
via a router/switch. CAN allows communication between several inverters.
Figure 2.3.15: Network connections
1. Slave inverter
2. Master inverter
3. CAN bus
4. Ethernet
5. Computer