32 Installation Guide THEIA HE-t String Inverters 357115.033, Issue 2.0, 2011 March
3.2. Self Test for Italy
The Self Test function is only valid for Italy. It tests the inverters’ grid monitoring function of
voltage and frequency, and takes approximately 2 minutes.
The Self-Test can only be activated when:
The installation procedure is executed
The country configuration is set to Italy
The inverter is in Running/Derating Mode.
Select: Commands>Inverter Commands>Self Test
Left – Cancel
Right – Ok
Enter – Confirm
The inverter carries out four test sequences, all of which are displayed on the screen.
After the test is finalized, each test result must be confirmed by entering Next.
After entering Finish on the last result, the screen displays the Inverter Commands menu.
The test results can be found in Commands>Inverter Commands>Results Self Test.
Refer to User Guide for more detailed information about the Italian Self Test.