Installation Guide THEIA HE-t String Inverters 357115.033, Issue 2.0, 2011 March 9
2.2. Mechanical Installation
Observe the following instructions when mounting and installing the THEIA HE-t inverter on
a suitable site. This is crucial to maintaining the efficiency of the inverter!
WARNING: Ensure a suitable mounting surface!
Correct installation prevents the inverter from falling from the wall. The mounting
surface must be suitable for the weight (20-22 kg / 44-49 lbs.) and temperature (90°
C / 194° F) of the inverter.
CAUTION: Ensure a suitable installation site!
Protect the inverter from flammable and explosive environments, as the inverter
heat sink can reach temperatures of up to 90° C / 194° F during long-periods of high
performance operation.
• Avoid enclosed areas with poor air flow! Sufficient ventilation is needed to prevent
temperature build up inside the inverter and hence possible power losses.
Observe the minimum distances specified below to maintain optimal cooling.
Figure 2.2.1: Minimum distances for optimum
cooling
1. 400 mm / 15.75 inches
2. 300 mm / 11.81 inches
3. 150 mm / 5.91 inches
4. 150 mm / 5.91 inches
CAUTION: Avoid installations with direct exposure to sunlight!
Direct sunlight may cause yield losses; direct sunlight causes increased internal
temperatures that can lead to reduced power output.
• For optimal operating conditions, the ambient temperature must be between -25° C & +65°
C / -13° F & 149° F, and non-condensing relative humidity between 4 % and 99 %.