DC Controller
UPC4 Master
User Manual
Page 13/100
©2010. ELTEK VALERE DEUTSCHLAND GmbH. UM_UPC4_V2.00_E_R1.1_2011-01-04
3.2.2.4 Fieldbus connectors
The UPC4 Master provides two different fieldbus connectors:
1.) Fieldbus connector RS485
The female connector RS485 (see Figure 3.) is designed to connect Modbus (Profibus is not
available at version 2.12).
Figure 4. Fieldbus female connector RS485
Pin assignme
nt of the RS485 connector:
Connector Pin Function
RS485
1 SHIELD
2 Not used
3 LINE B
4 RTS
5 GND
6 +5V
7 Not used
8 Line A
9 Not used
10 & 11 SHIELD
2.) Fieldbus connector MSTBO 2.5 (X8)
In addition the fieldbus can be also connected to the MSTBO 2.5 connector (X8) as show
n in Figure 5.
Pin assignment of the MSTB connector:
Connector Pin Function
X8 (Modbus)
1 Corresponds to RS485 SHIELD
2 Corresponds to RS485 LINE A
3 Corresponds to RS485 LINE B
4 Corresponds to RS485 GND
3.2.2.5 Hex switch 1 & Hex switch 2
If the field bus address is set to “0“ by software, the field bus address (that is a hexadecimal number)
must be set using hex switch 1 & 2. Switch 2 refers to the more significant nibble, whereas switch 1
refers to the lower significant nibble.
EXAMPLE: A
ddress “18” = 0x1 2
Hexswitch 1 = 2
Hexswitch 2 = 1
10
11
Comentarios a estos manuales