DC Controller
UPC4 Master
User Manual
Page 60/100
©2010. ELTEK VALERE DEUTSCHLAND GmbH. UM_UPC4_V2.00_E_R1.1_2011-01-04
6.5.2 Assignment Shunt*
(*2.7 or 2.10 is required)
In this menu the values of the connected
shu
nts are configured. The value of 60 A
(see the left-hand picture) means: If a
voltage value of 60mV falls at the shunt it
is interpreted as a current flow of 60 A.
The current values of the Basic-Units (BU)
are set a
t (9.11)
*2.7
.
The current values of the Battery
Monitoring
Boards (BMB) are set at
(9.12)
*2.10
.
9.11
9.12