DC Controller
UPC4 Master
User Manual
Page 53/100
©2010. ELTEK VALERE DEUTSCHLAND GmbH. UM_UPC4_V2.00_E_R1.1_2011-01-04
6.4.4 Service/Enable
In the area „Service/Enable“, additional
fun
ctions can be enabled at the UPC3.
If a parameter is set to „0“, the function is
disa
bled. If a parameter is set to “1” or
greater, the function is enabled.
A battery test (7.1) can be star
ted/stopped
in different ways at the UPC4:
-Start/stop via buttons of a display
pan
el/menu of the UPC4
- Start depending on date & time
- Start day to day
- Start/stop by an external command e.g.
config
uration software
- Start/stop by digital input (7.2)
The settings regarding starting/stopping of
"E
qualize charge" (7.3) are identical to the
battery test as described above.
For "Boost charg
e" (8.1) additional
conditions for starting & stopping are
possible:
- Start/stop via front buttons of a display
pan
el/menu of the UPC4
- Start if the battery voltage falls below the
value which is set at "Boost charge
" (see
section 6.10.3)
- Start after battery operation. If current is
withdraw
n from the Battery and the value is
greater than the value which is set at
"Thresholds
" (see section 6.6.1), the UPC
detects battery operation
- Start after mains error (optional, MMB is
requir
ed)
- Start/stop by an external command e.g.
config
uration software
- Start/stop by digital input
- Start/stop by battery current
- Start after b
attery test end (BtstE) by
declaration of the final criteria
- Start depending on date & time, for details
plea
se see "Boost charge
"
Duration time. Repetition interval
(day(s)),
please see "Boost charge
"
"Battery test", "Equalize charge" and "Boost charge" can be started/stopped via digital inputs (7.
2),
7.1
7.3
7.2
8.1
8.2
7.4