©2010. ELTEK VALERE DEUTSCHLAND GmbH. UM_UPC4_V2.00_E_R1.1_2011-01-04
Estimation of the discharge current
Calculation (example):
Battery 50 Ah
Nominal capacity 95% (5.2)
, see section 6.4.6.
Capacity= 47,5 Ah
Example: 20A are withdrawn from the fully charged battery for more than one minute.
For the calculation of factor F the accordant curre
nt values are used.
%)5030(*5
%)50130(*20
A
A
F
4F
FIbIest *
4*20Iest
80Iest
Ah 46,166 80/3600* 60 - 3600 *Ah 47,5
Estimation of the charge current
At charging the estimation is the other way round.
P= 50%
)30(*10
)130(*
pi
pib
F
8
9 F
Fl
)100/arg(** yeEfficiencChFlIbIest
Additional, parameter (2
8.5)
*9.9
(ChargeEfficiency) is introduced, because more energy is necessary to
charge a battery.
If the parameters (2
8.6)
*9.9
, (28.7)
*9.9
are under-run, in each case an event is generated.
6.10.5 SNMP*
(* requires 9.7), see section 6.4.4.
In this menu the SNMP relevant settings
are don
e.
Parameter "Manager" (29.1)
*9.7
is a
possibility to restrict the SNMP access to
the UPC4. If an IP is configured, it is only
possible to get access to the UPC4 by this
PC and by all configured trap receivers via
SNMP. Whereupon the manager is the only
one with write authorisation.
If IP = "0.0.0.0", this f
unction is disabled.
If (29.5)
*9.7
is empty, an SNMP requiry to Sysdescription iso(1).org(3).dod(6).internet(1).mgmt(2).mib-
29.1
29.2
29.3
29.4
29.5