DC Controller
UPC4 Master
User Manual
Page 88/100
©2010. ELTEK VALERE DEUTSCHLAND GmbH. UM_UPC4_V2.00_E_R1.1_2011-01-04
2134 Relay4.Q n/a Virtual relay 4, normally open contact (Q). For
details please see event no. 2128
2135 Relay4.Q' n/a Virtual relay 4, normally closed contact (Q'). For
details please see event no. 2129
2160 LVD active see LVD/PLD/Drop
diode
It signals, whether the LVD opto coupler is active
or not. Setta
ble via SNMP in the future.
2161 PLD1 active see LVD/PLD/Drop
diode
It signals, whether the PLD 1 opto coupler is
active or not. Settable via SNMP in the future.
2162 PLD2 active see LVD/PLD/Drop
diode
It signals, whether the PLD 2 opto coupler is
activ
e or not. Settable via SNMP in the future.
2163 Tsensor limit This event is active if one of the temperatures of
the general parameters has a temperature value
which is less than -50°C or greater than +150°C.
2164 Fan Rack: Error see CAN devices This event is active if one of the six fans of the up
to 16 possible fan tablets (FAN) signals an error.
2165 Fan Rack: No
CAN
see CAN devices This event is active if one of the up to 16 possible
fan tablets (FAN) has no CAN connection.
2166 BUI: Error state see CAN devices This event is active if one of the up to eight
possible Basic-Units (BU) signals an error.
2167 BUI: No CAN see CAN devices This event is active if one of the up to eight
possible Basic-Units (BU) has no CAN connection.
2168 STS: Error state see CAN devices This event is active if an STS signals an error.
2169 STS: No CAN see CAN devices This event is active if an STS has no CAN
connection.
2170 MMB: Error state see CAN devices This event is active if an MMB signals an error.
2171 MMB: No CAN see CAN devices This event is active if an MMB has no CAN
connection.
2172 BMB: Error state see CAN devices This event is active if a BMB signals an error.
2173 BMB: No CAN see CAN devices This event is active if a BMB has no CAN
connection.
2174 DIB: Error state see CAN devices This event is active if a DI8 signals an error.
2175 DIB: No CAN see CAN devices This event is active if a DI8 has no CAN
connection.
2176 RLB: Error state see CAN devices This event is active if an RLB signals an error.
2177 RLB: No CAN see CAN devices This event is active if an RLB has no CAN
connection.
2178 FMB: Error state see CAN devices This event is active if an FMB signals an error.
2179 FMB: No CAN see CAN devices This event is active if an FMB has no CAN
connection.
2180 UMB: ErrorState see CAN devices This event is active if an UMB signals an error.
2181 UMB: No CAN see CAN devices This event is active if an UMB has no CAN
connection.
2182 UMA: ErrorState see CAN devices This event is active if an UMA signals an error.
2183 UMA: No CAN see CAN devices This event is active if an UMA has no CAN
connection.
2184 RDX: Error state This event is active if an RD signals an error.
2185 RDX: No CAN This event is active if an RD has no CAN
connection. This CAN device is not stated at the
configuration. If no RD/RDP Display is connected
to the CAN bus, the signal "RDX: No CAN" will
always be active.
2186 RDP: Error state see Remote Display This event is active if an RDP signals an error.
2187 RDP: No CAN see Remote Display This event is active if an RDP has no CAN
connection.