DC Controller
UPC4 Master
User Manual
Page 14/100
©2010. ELTEK VALERE DEUTSCHLAND GmbH. UM_UPC4_V2.00_E_R1.1_2011-01-04
3.2.2.6 Function of the dip switches
The dip switches (see Figure 3.) are designed to terminate the field bus.
By switching switch 1 to
ON position the termination resistor of 120 is enabled. That is necessary if
the UPC4 master is one end of the field bus. In this case the field bus is either connected to the RS485
connector or to the MSTB connector.
If both connectors are used or e.g. a Y-cable is conne
cted to the RS485 connector the UPC4 master is
between two field bus nodes. In this case the termination resistor must be switched OFF by switch 1.
In order to enforce the idle level on the bus system at the period of time when no data transmitter is
activ
e, LINE B can be switched via a resistor of 1 k to ground by switch 2. LINE A can be switched via
a resistor of 1 k to VCC by switch 3. Whether this functionality is used or not depends on the bus
architecture as well on what the user wants. The enforced idle level should be carried out on the bus
once only.
3.2.2.7 Connector RS232 (Modem)
In addition to the Ethernet connector the UPC4 Master can be configured via RS232. In this case a “Null
Modem Cab
le” must be used for the connection to the configuration software MMT.
Furthermore a modem can be connected to the RS232 connector (see Figure 3.).
REMARK: The modem functionality is not supported at version 2.12.
For details please see section 6.1.1 “Configuration of UPC systems…
” and section 5.4.6 “control
function modem” as well.