6.6 Thresholds
6.6.1 Thresholds
With the exception of (10.4), (10.20) and
(10.21) all settings in this group serve for
generating events.
Battery
Exceeding the threshold of battery over
voltag
e "Vmax" (10.1) or falling below the
threshold of battery under voltage "Vmin"
(10.2) respectively battery warning
voltage "Vwarn" (10.3) activates the
related event in the signal matrix.
Parameter (10.4) defi
nines the over
voltage threshold at which the rectifiers
(REC) are switched OFF. 0= no REC switch
OFF.
At (10.1) and
(10.4) hysteresis (10.7) and
delay (10.5) is used.
At (10.2) hystere
sis (10.8) and delay
(10.6) is used.
At parameter (10.3) also h
ysteresis
according to (10.8) is used but no delay.
Battery temp.
"Temperature high" (10.9)
*5.1
relates to all
of the used temperature sensors. Enabling
of the individual sensors takes place in the
main menu "Battery
". Parameter (10.11)
*5.1
defines hysteresis whereas parameter
(10.10)
*5.1
defines delay.