
DC Controller
UPC4 Master
User Manual
Page 36/100
©2010. ELTEK VALERE DEUTSCHLAND GmbH. UM_UPC4_V2.00_E_R1.1_2011-01-04
5.4.4 Control function "Hand-op. charge"
(Only available if "Hand-op. charge" is enabled).
(1)* "Log in" coul
d be necessary, see section 5.4.7 Log in.
(2)* The scre
en automatically changes to the next.
In the top line the default voltage of the rectifiers is shown.
In the second line the present measured values are shown.
(3)* By pressing the arrow
keys the default voltage value of the rectifiers is changed.
(4)* At this p
osition hand operation charge is stopped.
5.4.5 Control function "System test"
(Only available if "System test" is enabled).
(1)* The scre
en automatically changes to the next.
In the top line the default voltage of the rectifiers is shown.
In the second line the measured values are shown.
(2)* By pressing the arrow
keys the default voltage value of the rectifiers is changed.
(3)* At this p
osition system test is stopped.
UPC4 12.07.10
OKAY 11:47:36
x times ▼
ENT
Control Function
->System test
System test start
Act.: 20.0A 54,0V
▼▲
Nomin.: 54,0V
Act.:20.0A 54,0V
Nomin.: 54,2V
Act.:20.0A 54,2V
Automatic
1
*
ENT (3)*
System test start
Act.: 20.0A 54,2V
2x ESC
(2)*
UPC4 12.07.10
OKAY 11:47:36
x times ▼
ENT (1)*
Control Function
► Hand-op. char
Hand-op. char start
Act.: 20.0A 54,0V
▼▲
Nomin.: 54,0V
Act.:20.0A 54,0V
Nomin.: 54,2V
Act.:20.0A 54,2V
Automatic
2
*
ENT (4)*
Hand-op. char start
Act.: 20.0A 54,2V
2x ESC
(3)*
Comentarios a estos manuales