DC Controller
UPC4 Master
User Manual
Page 57/100
©2010. ELTEK VALERE DEUTSCHLAND GmbH. UM_UPC4_V2.00_E_R1.1_2011-01-04
Legend:
Vtapp = Measured tapped voltage value against (–)
Vbatt = Measured battery voltage
Batc = Number of batteries (value has to be set)
Ctapp = Tapping point counted from (-), value has to be set
Vplus = Calculated tapped voltage value against (+)
(a) Asymmetry calculation with tapping point at the center of the battery:
xVtappVbattDiff 2
If the difference (without consideration of sign) is greater than (5.5), asymmetry is indicated then.
(b) Asymmetry calculation with tapping point not at the center of the battery:
))((*)(2 CtappBatcCtapp
Batc
Vbatt
VtappVbattVtapp
Vtapp2 is the battery tapping voltage against (+), calculated with consideration of a correction factor.
2VtappVtappDiff
If the difference (without consideration of sign) is greater than (5.5), asymmetry is indicated then.
NOTE:
If "Battery Unsymm." (5.5) e.g. is set to 2V, the measured value may differ
at +/- 1V related to the calculated unsymmetry voltage.
The detection of an opened/tripped
battery fuse is only possible if the battery
tap is located behind the battery fuse. If
the difference between system- and
battery voltage is greater than parameter
“Vdiff Fuse case” (6.1) and the battery
current less than parameter “Itrigg fuse
case” (6.2), the event “Fuse open“ is
activated.
For the t
emperature compensation of the
charge voltage the temperature sensor
(6.3) of a battery has to be activated first,
e.g. "Batt1".
The temperature coefficient "Tk (per cell)"
(6.4) and "Ba
se temp. Tcomp" (6.5) depend
on the battery and have to be asked at the
manufacturer.
6.1
6.2
6.3
6.4
6.5
6.6
6.7