Eltek Valere UNV-F 2.5 Manual de usuario Pagina 21

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 100
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 20
DC Controller
UPC4 Master
User Manual
Page 21/100
©2010. ELTEK VALERE DEUTSCHLAND GmbH. UM_UPC4_V2.00_E_R1.1_2011-01-04
4.3.2 Charge current limitation
Figure 7. Diagram “Charge current limitation”
Discharged batteries, e.g. after backup operation, are charged with an adjustable maximum current
unti
l the value of the temperature-controlled trickle charge voltage is reached. The battery voltage is
measured at the beginning of the battery charging. Commencing with this battery voltage, the output
voltage of the rectifiers is increased accordingly so that the set maximum of the battery charging
current is reached. This process is retained as long as the output voltage has reached the value of the
trickle charge voltage (temperature-controlled).
(For details please see section 6.4.3 Charge Control
).
4.3.3 Autarkic rectifier operation
(Emergency operation)
If the rectifiers do not receive a control signal, e.g. because of
breakdown of the UPC4,
breakdown of the CAN-Bus connection (e.g. cable break),
the rectifiers self-acting return to a constant output voltage as default.
Example: Rectifiers of a 48 VDC system return to default voltage value of 54.5 V (factory preset).
At battery backed systems this operating mode should be seen as an emergency operation.
4.3.4 PLD function (Power Load Disconnect)
The PLD function makes it possible to disconnect inferior priority loads during battery backed
operation. Due to this the backup time of more important loads is extended.
There is the possibility to configure up to two consu
mer load levels (inferior priority loads)
independently of each other.
The following criteria for PLD recognition are available:
PLD recognition at under-run of an adjustable voltage threshold, reset after exceeding the
adjusted voltage threshold.
PLD recognition at detection of battery operation after expiration of an adjustable time delay,
reset after ending of battery operation.