DC Controller
UPC4 Master
User Manual
Page 89/100
©2010. ELTEK VALERE DEUTSCHLAND GmbH. UM_UPC4_V2.00_E_R1.1_2011-01-04
2188 1.L1
V<>Vmin,max
see Mains monitoring This event is active if AC voltage of the 1. phase
of mains 1 is less than the minimum voltage or
greater than the maximum voltage. One common
delay and one hysteresis of the min. and one
hysteresis of the max. voltage are available. The
min. and max. voltage values as well are built
using the nominal mains voltage with the help of
two settable tolerance values. In order to set this
event it is necessary that "set via digital input" is
disabled, monitoring of this phase is enabled, and
the assigned mains monitoring board (MMB) is
enabled as well. Furthermore this event can be
directly set via digital input.
2189 1.L2
V<>Vmin,max
see Mains monitoring 2. phase of mains 1, for details please see event
no. 2188.
2190 1.L3
V<>Vmin,max
see Mains monitoring 3. phase of mains 1, for details please see event
no. 2188.
2191 2.L1
V<>Vmin,max
see Mains monitoring 1. phase of mains 2, for details please see event
no. 2188.
2192 2.L2
V<>Vmin,max
see Mains monitoring 2. phase of mains 2, for details please see event
no. 2188.
2193 2.L3
V<>Vmin,max
see Mains monitoring 3. phase of mains 2, for details please see event
no. 2188.
2194 error bool seq. see Signals enable This event is active if there is a syntax error in the
configured bool sequence.
2195 combined Error 1 see Signals enable Boolean expression 1 is active. Currently not
available for the common user.
2196 combined Error 2 see Signals enable Boolean expression 2 is active. Currently not
available for the common user.
2197 combined Error 3 see Signals enable Boolean expression 3 is active. Currently not
available for the common user.
2198 combined Error 4 see Signals enable Boolean expression 4 is active. Currently not
available for the common user.
2199 combined Error 5 see Signals enable Boolean expression 5 is active. Currently not
available for the common user.
2200 UPC Supply 1 Err This event is active if the first internal power
supply signals an error.
2201 UPC Supply 2 Err This event is active if the second internal power
supply signals an error.
2202 UPC Supply 3 Err This event is active if the third internal power
supply signals an error.