6.10.8 MMB*/Mains monitoring
MMB* (requires 2.9), see section 6.4.2.
In connection with an optional available
Mains Monitoring Board (MMB) the UPC4 is
able
to detect mains failure or phase break
down. The mains failure is available as
event and can also be used as source for
„PLD/LVD
“ function, see section 6.8.
By the use of mains monitoring boards the
voltag
es of each phase are measured.
The threshold values V< (32.1)
*2.9
and V>
(32.2)
*2.9
are related to the nominal voltage
of the inverters, which is set in the area
"System parameters
".
A mains failure is detected if these values
are exceeded/under-run, with inclusion of
the parameters
(32.3)
*2.9
, (32.4)
*2.9
, and
(32.5)
*2.9
.
The monitoring of single phases can be
enabled/disabled by parameter (32.6)
*2.9
.
The phases 1A to 3A belong to the MM
board A, the phases 1B to 3B belong to the
MM board B.
If an ext
ernal mains monitoring module is
used: The digital input which is connected
to the external mains monitoring module
can be defined by parameter (32.7).
32.1
32.2
32.5
32.4
32.3
32.6
32.7