
DC Controller
UPC4 Master
User Manual
Page 66/100
©2010. ELTEK VALERE DEUTSCHLAND GmbH. UM_UPC4_V2.00_E_R1.1_2011-01-04
"LVD":
Selection source V1 (default battery voltage) as well
as event “LVD active” is assigned to the LVD
relay (e.g. K1).
The LVD contactor (energized by relay) switches off a
s soon as the battery voltage drops below the
limit „Low limit OFF“ (20.1) and additionally "Drop delay" (20.5) has been elapsed.
Reactivation of the contactor takes place if „Low limit ON“ (20.2) has be
en exceeded.
"PLD":
The PLD contactor (energized by relay) switches off as soon as the battery voltage drops below the
limit „Low lim
it OFF“ (20.6) and additionally "Drop delay" (20.7) has been elapsed.
Reactivation of the contactor takes place if „Low limit ON“ (20.
9) and the set "Connect delay"(20.10)
as well has been exceeded.
PLD2 has the same setting options as PLD1.
ATTENTION!
Because the battery voltage directly increases after power load
disconnection, the switch-on voltage "Low limit ON" (20.2) should be set to a
value great enough to avoid direct activation of the contactors.
Drop diodes in UPS systems are used to
protect the consumer load against
overvoltage, e.g. during boost charge.
First of all the voltage reference (21.1)
(1=Vbatt; 2=Vtapp; 3=Vload) and
following the ON (21.2) and OFF (21.3)
threshold is set for drop diode 1 as well as
for drop diode 2 if applicable.
21.1
21.2
21.3
Comentarios a estos manuales