Eltek Valere UNV-F 2.5 Manual de usuario Pagina 52

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 100
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 51
DC Controller
UPC4 Master
User Manual
Page 52/100
©2010. ELTEK VALERE DEUTSCHLAND GmbH. UM_UPC4_V2.00_E_R1.1_2011-01-04
Optional CAN devices (modules):
CAN device item Comment
BU Basic Unit
(2.7)
Modular measuring board. E.g. for battery monitoring
STS Bypass
(2.8)
Active Static Bypass Switch (mains <—> inverter)
MMB MainsMonitor
(2.9)
Mains monitoring (AC input)
BMB AnalogInputs
(2.10)
Extension of the measuring inputs for battery monitoring
DIB Digital Input
(2.11)
Extension of the digital inputs
RLB Relais Outp
(2.12)
Extension o
f
the relays
FMB Fuse Board
(2.13)
Extension o
f
fuse monitoring
FAN tray
(2.14)
Active fan tablet
UMB
(2.15)
Extension measuring control (only used for CONB03)
UMA
(2.16)
Extension measuring control (only used for CONB03)
6.4.3 Charge control
The main function of the UPC4 is, to deliver a
voltag
e default value to the rectifiers, in
order to charge batteries or to keep them
under good charge conditions.
This regulator (see the picture on the left)
p
rovides several additional functions. After a
restart, the system overtakes the measured
voltage as start voltage for the regulator.
Every second the voltage default value is
controll
ed (up/down) at the value (3.6) if
deviations of the current default value exist.
For trickle charge the adjusted relative
current default value (3.1) is used.
For an activated boost charge and equalize
charge respectively the raised charge
current (3.2)
*8.1
and (3.3)
*7.3
respectively is
used.
If a diesel generator is used for power supply, the default value (3.4) i
s used. The digital input (3.5)
indicates a working diesel generator. This function is disabled, if the digital input is set to “0”.
The configured value of the norminal battery capacity (see item (5.2)
at section 6.4.6) is used as point
of reference for the relative charge currents.
3.1
3.6
3.2
3.4
3.5
3.3