DC Controller
UPC4 Master
User Manual
Page 18/100
©2010. ELTEK VALERE DEUTSCHLAND GmbH. UM_UPC4_V2.00_E_R1.1_2011-01-04
4.2.2 Rectifiers of the Flat-, Mini-, Micro-, and Powerpack group
The UPC4 supports all rectifiers of the Flat-, Mini-, Micro-, and Powerpack group at its second CAN bus
port "CAN 3 & CAN 4" (RJ45 connectors).
Compared to the PSR rectifiers (see section 4.2.1 Rectifiers of the PSR/PSS group
) the slots of the
xxpack rectifiers have no fixed CAN addresses. Therefore the log on procedure between UPC4 and
these types of rectifiers is different.
If a rectifier is plugged to a backplane slot, the rectifier logs automatically on to the UPC4 transmitting
its se
rial number. After it has logged on the rectifier is controlled by the UPC4. The communication
between UPC4 and rectifier takes place using the serial number.
(For details please see section 6.4.2 CAN Devices Cnt
).
4.2.3 Monitoring of load sharing of the rectifiers
With the assistance of this functionality it is possible to monitor the load utilization of each individual
rectifier (REC). For this a changeable threshold (in percent) has to be set at the menu item "System
parameters" (section 6.4.5).
The UPC calculates the percentages of the difference of the maximum current of a rectifier and the
mini
mum current of one rectifier compared to the maximum current of one rectifier.
If the settable percentaged value is exceeded, the
UPC generates the event "RECLoadDistrib".
For details please see "System parameters
" (section 6.4.5).