6.11.5 Text Digital input*
(* requires 2.11), see section 6.4.2.
If digital input boards (DI8
) are used, it is
possible to assign individual texts to the
digital inputs. These texts then also appear
in the failure/event list.
For each individual digital input two texts
are avai
lable. Text 1 is used if an event is
active
, text 2 is used if an event is inactive.
The texts (
38.1)
*2.11
, (38.3)
*2.11
are related
to the digital inputs of the first DI8, the
texts (38.2)
*2.11
, (38.4)
*2.11
are related to
the digital inputs of the second DI8.
Example 1
:
A switch (normally open contact) is connected to the digita
l input 1.1; the input is not inverted by
configuration.
First case: The switch is not activated.
>No event is generated; status text input 1.1 of (3
8.3) is used.
Second case: The switch is activated
>An event is generated; status text fail input 1.1 of (38.1) is used.
Example 2
:
A switch (normally closed contact) is connected to the digita
l input 1.2; the input is not inverted by
configuration.
First case: The switch is not activated.
>An event is generated; status text fail input 1.2 of (38.1) is used.
Second case: The switch is activated.
>No event is generated; status text input 1.2 of (3
8.3) is used.
Example 3
:
A switch (normally closed contact) is connected to the dig
ital input 1.3; the input is inverted by
configuration.
First case: The switch is not activated.
>An event is not generated; status text input 1.3 of (38.3) is used.
Second case: The switch is activated.
>An event is generated; status text fail input 1.3 of (38.1) is used.