DC Controller
UPC4 Master
User Manual
Page 30/100
©2010. ELTEK VALERE DEUTSCHLAND GmbH. UM_UPC4_V2.00_E_R1.1_2011-01-04
Rectifiers of the series PSR & PSS are in the group "R#1". The abbreviation for those rectifiers is "R#1".
Rectifiers of the series Micro-, Mini-, Flat-, and Powerpack are in the group "R#2". The abbreviation for
those re
ctifiers is "R#2".
5.3 Operating status
In this menu block information about the actual operating status of the system can be queried.
Operating status:
Digital inputs: Stat
us active/inactive of the digital inputs (digital extension modules are
required).
Relay outputs: Sta
tus of the relays: active/inactive.
FM board: St
atus active/inactive of the fuse monitoring board.
Failure list: The fail
ure list shows the active alarms.
Event list: Th
e event list shows all stored events (date/time, appearance/disappearance).
Fan racks: Sh
ow „Okay“ or „Failure“ of each of the connected fan racks.
Battery te
st: Battery test active = ’*’, inactive = ’ -’. Furthermore the withdrawn capacity (Ah) is
shown.
Capacity calculator:
Shows the available capacity of the complete system or of individual
battery strings.
Data memory: Shows wh
ether data currently are stored or not. ’ OFF/ON’
Boost charge: Boost char
ge active = ’*’, inactive = ’ -’
Equalize charge: Compen
sating charge.
Manual operation: Manu
al charge of the batteries.
System test:
Test of the system.
Modem: Sho
ws the initialisation status of the external or internal modem.
5.3.1 Event list
(1)* The a
ppeared event is shown. Within the squared bracked the ecplicit event number is shown. The
numeral behind "#" indicates the quantity of the events. " ->" indicates that the event is active, "<-"
indicates that the event is inactive.
(2)* Indicat
es the date of the recorded event.
(3)* If the ev
ent list is to be deleated, a log in could be necessary, see section 5.4.7 Log in.
UPC4 12.07.10
OKAY 11:47:36
▼
ENT
OperatingStatus
►Event List
Vlo < Vmin
->[3000] #5
ENT
27.10.2010
8:11:26
Delete History?
No/Yes: ESC/ENT
ENT
ENT
Login procedure
►User1
x times▼
INV No CAN
->[3041] #5
27.10.2010
9:10:05
ENT
INV No CAN
<-[3041] #5
27.10.2010
10:10:05
ENT
More events
▲
▲
▲
ESC
1
*
2
*
3
*