DC Controller
UPC4 Master
User Manual
Page 75/100
©2010. ELTEK VALERE DEUTSCHLAND GmbH. UM_UPC4_V2.00_E_R1.1_2011-01-04
6.10.9 Hand operation charge*
Enabling of "Hand operation charge" has to
be set at Service/Enable
(*requires 9.1),
see section 6.4.4.
During hand operation charge the
autom
atic control of the rectifiers is invalid
and therefore it is possible to charge the
batteries manually using the RDD and RDP
as well. In this case the user has to set the
charge voltage value manually at the
RDD/RDP.
The last used voltage value of the trickle charge i
s assumed by the UPC4 as minimum voltage value
for hand operation charge. This value can be set up to a maximum of parameter "Max. charge volt"
(33.6). If the actual measured battery voltage value is greater about (33.3) than the manually set
voltage, the hand operation charge is interrupted immediately. If (33.1) is set to "0", the following
listed events are inhibited during hand operation charge and delayed according to parameter (33.4)
after hand operation charge is finished: "Vbatt > Vmax", "Vload > Vlmax", "Vtapp > Vomax".
During hand operation charge the nominal current value of the rectifiers can be reduced manually by
parameter (
33.5). But if this value exceeds the maximum possible current of the module, it has no
effect. This value is valid per each rectifier.
6.10.10 System test*
(* requires 9.2), see section 6.4.4.
During "system test" the automatic control
of the re
ctifiers is invalid and therefore it is
possible to control the rectifier voltage
manually using the RDD: The user is able to
set the rectifier voltage value manually at
the RDD within the thresholds (34.5),
(34.6) in order to test the system.
If (34.1) is set to "0", the following listed events are inhibited during system test is running and
delayed according to parameter (34.3) after system test is finished:
"Vbatt < Vmin", "Vbatt > Vmax", "Vload < Vlmin", "Vload > Vlmax", "Vtapp <
Vomin", "Vtapp > Vomax".
During system test the nominal current value of the
rectifiers can be reduced manually by parameter
(34.4). But if this value exceeds the maximum possible current of the module, it has no effect. This
value is valid per each rectifier.
33.1
33.2
33.6
33.4
33.5
33.3
34.1
34.5
34.2
34.6
34.4
34.3