DC Controller
UPC4 Master
User Manual
Page 90/100
©2010. ELTEK VALERE DEUTSCHLAND GmbH. UM_UPC4_V2.00_E_R1.1_2011-01-04
8.2 System
Event-
no.
Event text Reference to
parameter
Description
3000 Vload < Vmin see Thresholds This event is active if the load voltage of the system
is less or equal to the minimum load voltage "Vmin". A
configurable delay and hysteresis as well is available.
In order to activate this signal, the parameter alar
m
at over voltage - system test of system [1] has to be
set to "1" or alarm delay - system test of system [1]
is elapsed. Additionally no battery test of system [1]
may be active.
3001 Vload > Vmax see Thresholds Load voltage > Vmax. Detail s. Event no. 3000
3002 Vload < Vmin_INV see Thresholds Load voltage < Vmin_INV. Detail s. Event no. 3000
3003 Vload < Vmin_DCC see Thresholds Load voltage < Vmin_DCC. Detail s. Event no. 3000
3010 REC#1 Error REC signals error
3011 REC#1 No CAN One or more REC have no CAN connection
3012 REC#1
Redundancy
see CAN devices REC redundancy error
3013 REC#1 Load REC load limit exceeded
3014 REC#1 Load
distrib
REC load distribution not ok
3020 REC#2 Error REC signals error
3021 REC#2 No CAN One or more REC have no CAN connection
3022 REC#2
Redundancy
see CAN devices REC redundancy error
3023 REC#2 Load REC load limit exceeded
3024 REC#2 Load
distrib
REC load distribution not ok
3030 Lim Load current
3035 DCC Error DC/DC converter signals error
3036 DCC No CAN One or more DC/DC converter(s) have no CAN
connection
3037 DCC Redundancy see CAN devices DC/DC converter redundancy error
3040 INV Error Inverter signals error
3041 INV No CAN One or more inverter(s) have no CAN connection
3042 INV Redundancy see CAN devices Inverter redundancy error
3043 Equalize charge s. Equalize charge Equalize charge is running
3044 Equal.ch.Timeout s. Equalize charge Equalize charge time limit is reached
3045 Boost charge s. Boost charge Boost charge is running
3046 Boost ch Timeout s. Boost charge Boost charge time limit is reached
3047 Fan (boost chge) Fan boost charge is active
3051 Insulation err P s. Thresholds Insulation error against plus
3052 Insulation err M s. Thresholds Insulation error against minus
3053 Isol. meas. runs s. Thresholds Isolation measurement is active
3056 Battery test s. Battery test Battery test is running
3057 Battery test err s. Battery test The last battery test has been finished faultily
3060 Drop diode 1 s. LVD/PLD/Drop d. Drop diode 1 is active
3061 Drop diode 2 s. LVD/PLD/Drop d. Drop diode 2 is active
3064 Difference Ah
(9.3)
This event ist active if the service "energy balance"
detects a difference of the capacity (Ah) of the
batteries of system [1] compared with the set value
at parameter "Difference Ah".